The MultiPlus-II combines the functions of the MultiPlus and the MultiGrid. It has all the features of the MultiPlus, plus an external current transformer option to implement PowerControl and PowerAssist and optimise self-consumption with external current sensing (max 32A). It also carries all the MultiGrid features, with built-in anti-islanding and a growing list of country grid approvals.
PowerAssist prevents overload of a limited AC source, such as a generator or shore power connection. Battery charging is automatically reduced first to avoid an overload; if demand still peaks, the unit boosts the output with power taken from the battery.
ESS (Energy Storage Systems): the MultiPlus-II is the key component in a Victron ESS, combining flexibly with MPPT solar chargers or grid-tie PV inverters.
Uninterrupted AC power (UPS function): if grid, shore or generator power fails, the inverter takes over the connected loads in under 20 milliseconds, so computers and other electronics keep running without disruption.
Remote monitoring and control: monitor and control the system locally or remotely via the free VRM app and VRM portal, from a phone, tablet, laptop or PC, with a Cerbo GX or Venus GX for full control including automatic generator start.
Specification
- Battery voltage: 24V nominal
- Continuous power (25°C): 3,000 VA / 2,400 W
- Continuous power (40°C): 2,200 W, (65°C): 1,700 W
- Peak power: 5,500 W
- Maximum efficiency: 94%
- Maximum battery charge current: 70A, adaptive 4-stage charge algorithm
- Charge voltages: absorption 28.8V, float 27.6V, storage 26.4V
- AC transfer switch rating: 32A, max AC input current 32A
- DC input voltage range: 19-33V
- AC output: 230V, 50Hz
- AC input voltage range: 187-265V, frequency range 45-65Hz
- Zero load power: 13W (9W AES, 3W in Search Mode)
- Communication port: VE.Bus
- Number of AC outputs: 2, plus auxiliary output
- External AC current sensor option: 50A or 100A
- Protections: output short-circuit, overload, high/low battery voltage, over temperature, AC voltage on inverter output, excessive DC ripple
- Operating temperature: -40°C to 65°C, fan-assisted cooling
- Protection category: IP22
- Dimensions: 499 x 268 x 141 mm
- Weight: 19 kg
- Material: steel, blue (RAL 5012)
- Compliance: EN-IEC 60335-1, EN-IEC 60335-2-29, EN-IEC 62109-1, EN-IEC 62109-2
- Warranty: 5 years standard (extendable to 10 years); lead-acid batteries 2 years, lithium batteries 3 years
Recommended DC fuse: 300A with holder. Use 50mm² cable for runs up to 5m, or 95mm² for 5-10m; battery connection is via M8 bolts.